2. SETTING
IMCB04-E9
21
(6) AH2 (Second alarm [ALM2] differential gap setting) *
Setting range
TC and RTD inputs: 0 to 100 °C [°F] or 0.0 to 100.0 °C [°F]
Voltage and current inputs: 0.0 to 10.0 % of span
Factory set value
TC and RTD inputs: 2 °C [°F] or 2.0 °C [°F]
Voltage and current inputs: 0.2 %
* Not displayed when there is no second alarm (ALM2).
(7) CTr (CT ratio setting) *
Set the number of times that a wire is wound on to the hole of a CT.
Setting range: 0 to 9999
Factory set value: CTL-6-P-N: 800
CTL-12-S56-10L-N: 1000
*
Not displayed when there is no heater break alarm (HBA).
(8) dF (Digital filter setting)
Setting range: 0 to 100 sec (If 0 is set, the PV digital filter is turned off.)
Factory set value:1
(9) STTM (Time factor assumed to be safe)*
As this factor is so adjusted that the self-tuning result optimum to most controlled-objects is
obtained, do not change it.
This is the factor to adjust the reference time of establishing the stabilized state of a measured value.
The larger the set value, the longer the time until the measured value is stabilized.
Setting range: 0 to 200
Factory set value: 100
*
Displayed when the self-tuning is provided.