EasyManua.ls Logo

RKC INSTRUMENT CB100 - Selecting Method; Selecting Procedure Details

RKC INSTRUMENT CB100
38 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
24
IMCB04-E9
3. COMMUNICATION INITIAL IDENTIFIER
!
! !
! List of Communication Initialize Identifiers
Note that there are identifiers which cannot be communicated depending on the
specification. For details on the structure of communication data, see the instruction manual
for CB100/CB400/CB500/CB700/CB900 Communication Instruction Manual
[IMCB03-E#
##
#].
The number of digits is 6 for all data.
ID: Identifier (RO: Read only R/W: Read/write)
Name ID Data range Factory
set value
R/W
Initialization mode selection IO 0: RO 1: R/W 0 R/W
Setting necessary code [Cod] IP 0 to 2 0 R/W
Input type selection [SL1] XI 0 to 15 See *1
To vary
depending on
the
specification
R/W
Engineering unit and cooling type
selection [SL2]
XQ 0: °C (Air cooling)
1: °F (Air cooling)
2: °C (Water cooling)
3: °F (Water cooling)
To vary
depending on
the
specification
R/W
Heater break alarm (HBA),
control loop break alarm (LBA),
special specification, or
control loop break alarm (LBA)
output selection [SL3]
LV 0: No function provided
1: HBA provided
2: LBA provided, LBA is output
from first alarm
5: HBA (Z-132 specification)
provided
10: LBA provided, LBA is
output from second alarm
To vary
depending on
the
specification
R/W
First alarm (ALM1) type or
First alarm (ALM1) with hold action
selection [SL4]
XA 0 to 15 See *2
To vary
depending on
the
specification
R/W
Second alarm (ALM2) type or
Second alarm (ALM2) with hold
action selection [SL5]
XB 0 to 15 See *2
To vary
depending on
the
specification
R/W
Continued on the next page.

Table of Contents

Other manuals for RKC INSTRUMENT CB100

Related product manuals