2. SETTING
IMCB04-E9
12
(7) SL7 (Energized/de-energized selection, special specification selection 1)
The following instrument is set to 0000.
Instrument without both the first alarm (ALM1) output and the second alarm (ALM2) output.
Factory set value varies depending on the instrument specification.
Set value Description
0 First alarm energized alarm First alarm energized/
1 First alarm de-energized alarm de-energized alarm selection
0 Second alarm energized alarm Second alarm energized/
1 Second alarm de-energized alarm de-energized alarm selection
0 First alarm Z-124 specification not provided *
1
First alarm special
1 First alarm Z-124 specification provided *
2
specification selection
0 Second alarm Z-124 specification not provided *
1
Second alarm special
1 Second alarm Z-124 specification provided *
2
specification selection
*1 The alarm output is forcibly turned on when the burnout function is activated.
*2 No alarm action is taken by the burnout function. (Same as the normal alarm action.)
(8) SL8 (Special specification selection 2)
Any digits other than the tens digit are not used. As malfunction may result, do not change
any of other digits.
Factory set value varies depending on the instrument specification.
Set value Description
0 Z-185 specification not provided *
1
Special specification selection
1 Z-185 specification provided *2
00 000!0 Fixed
*1 For control actions of the F or D type, normal control is performed regardless of the activation of
the burnout function. For control actions of the A or W type, both outputs on the heat and cool
sides are turned off.
*2 The control output is forcibly turned off when the burnout function is activated.