2. SETTING
IMCB04-E9
14
(11) SL11 (SV alarm type selection)
The following instrument always set it to 0 : First alarm, SV alarm not provided.
• Instrument without the first alarm (ALM1) output.
• Instrument of the process alarm, deviation alarm, band alarm or control loop break alarm
(LBA) is used as the first alarm (ALM1).
The following instrument always set it to 0 : second alarm, SV alarm not provided.
• Instrument without the second alarm (ALM2) output.
• Instrument of the process alarm, deviation alarm, band alarm, heater break alarm (HBA) or
control loop break alarm (LBA) is used as the second alarm (ALM2).
• Instrument with the Z-168 specification.
The following conditions must be satisfied in order to effectuate SV alarm.
• SL4 (First alarm [ALM1] type selection, hold action selection) should be set to 0000. The
content of the SL4 setting has priority over that of the SL11 setting.
• SL5 (Second alarm [ALM2] type selection, hold action selection) should be set to 0000.
The content of the SL5 setting has priority over that of the SL11 setting.
Factory set value varies depending on the instrument specification.
Set value Description
0 First alarm, SV alarm not provided First alarm, SV alarm selection
1 First alarm, SV alarm provided
0 First alarm, SV high alarm First alarm, SV alarm type selection
1 First alarm, SV low alarm
0 Second alarm, SV alarm not provided Second alarm, SV alarm selection
1 Second alarm, SV alarm provided
0 Second alarm, SV high alarm Second alarm, SV alarm type selection
1 Second alarm, SV low alarm