3. COMMUNICATION INITIAL IDENTIFIER
IMCB04-E9
27
*
2 0: No alarm 7: Process low alarm
1: Deviation high alarm 9: Deviation high alarm with hold action
2: Deviation high/low alarm 10: Deviation high/low alarm with hold action
3: Process high alarm 11: Process high alarm with hold action
5: Deviation low alarm 13: Deviation low alarm with hold action
6: Band alarm 15: Process low alarm with hold action
Do not set 4, 8, 12 or 14. Malfunction may result.
*3 0: PID action with autotuning (Direct action), time proportioning output (relay contact output,
voltage pulse output, trigger (for triac driving) output or triac output.
1: PID action with autotuning (Reverse action), time proportioning output (relay contact output,
voltage pulse output, trigger (for triac driving) output or triac output.
3: Heat/cool PID action with autotuning, heat-side time proportioning output (relay contact
output, voltage pulse output or triac output) or cool-side time proportioning output (relay
contact output, voltage pulse output, triac output).
4: PID action with autotuning (Direct action) or current output.
5: PID action with autotuning (Reverse action) or current output.
7: Heat/cool PID action with autotuning, heat-side current output or cool-side time
proportioning output (relay contact output, voltage pulse output, triac output).
11: Heat/cool PID action with autotuning, heat-side time proportioning output (relay contact
output, voltage pulse output or triac output) or cool-side current output.
15: Heat/cool PID action with autotuning, heat-side current output or cool-side current output.
Do not set 2, 6, 8, 9, 10, 12, 13 or 14. Malfunction may result.
*4 0: First alarm (Energized alarm), second alarm (Energized alarm)
1: First alarm (De-energized alarm), second alarm (Energized alarm)
2: First alarm (Energized alarm), second alarm (De-energized alarm)
3: First alarm (De-energized alarm), second alarm (De-energized alarm)
4: First alarm (Energized alarm, Z-124 specification provided), second alarm (Energized alarm)
5: First alarm (De-energized alarm, Z-124 specification provided), second alarm (Energized
alarm)
6: First alarm (Energized alarm, Z-124 specification provided), second alarm (De-energized
alarm)
7: First alarm (De-energized alarm, Z-124 specification provided), second alarm (De-energized
alarm)
8: First alarm (Energized alarm), second alarm (Energized alarm, Z-124 specification provided)
Continued on the next page.