3. COMMUNICATION INITIAL IDENTIFIER
IMCB04-E9
26
ID: Identifier (RO: Read only R/W: Read/write)
Name ID Data range Factory
set value
R/W
Time factor assumed to be safe
[STTM]
GH 0 to 200 100 R/W
Factor to calculate proportional band
[STPK]
PU 0 to 200 67 R/W
Factor to calculate integral time[STIK] IU 0 to 200 16 R/W
Integral time limiter [ILIM] IL 4 to 3600 seconds 3600
Z-1022
specification:
500
R/W
Holding peak ambient temperature
[TCJ]
HP 10 to +100 °C0RO
Operating time display unit
(Upper digits) [WTH]
UT 0 to 10 0 RO
Operating time display unit
(Lower digits) [WTL]
UU 0 to 9999 0 RO
*1 Input type table
Input type Set value
K0
J1
L2
E3
N4
T5
U6
R7
S8
B*A9
W5Re/W26Re *A 10
Thermocouple
input (TC)
PL II 11
Pt100 (JIS/IEC)
12
RTD input
(RTD)
JPt100 (JIS)
13
0 to 5 V DC 14
Voltage input 0 to 10 V DC *B 14
1 to 5 V DC 15
0 to 20 mA DC 14Current input
4 to 20 mA DC 15
*A Cant be selected for the instrument with the modbus communication specification (Z-1021
specification).
*B To be fixed to 14 for the 0 to 10 V DC (Z-1010 specification). No input type cannot be changed