2. SETTING
IMCB04-E9
11
(6) SL6 (Control action type selection)
Conduct setting so as to meet the instrument specification. An incorrect setting may cause a
malfunction.
When control action is of the type D or F, Control action type selection (Cool-side) setting is
ignored.
Factory set value varies depending on the instrument specification.
Set value Description
0
Direct action (D type)
Direct/reverse action
1
Reverse action (F, A and W type)
selection
0
PID action with autotuning (D, F type) *
1 Control action type
1
Heat/Cool PID action with autotuning (A, W type) *
2 selection
0
Heat-side time proportioning output (M, V, G, T output) *
3,*4 Control output type
1
Heat-side continuous output
(Current output: 4 to 20 mA DC)
selection (Heat-side)
0
Cool-side time proportioning output (M, V, T output) *
3 Control output type
1
Cool-side continuous output
(Current output: 4 to 20 mA DC)
selection (Cool-side)
*1 D type: PID action with autotuning (Direct action)
F type: PID action with autotuning (Reverse action)
*2 A type: Heat/cool PID action with autotuning (Air cooling)
W type: Heat/cool PID action with autotuning (Water cooling)
*3 M output: Relay contact output G output: Trigger output for triac driving
V output: Voltage pulse output T output: Triac output
*4 The G output cannot be selected in the heat/cool control.