3. COMMUNICATION INITIAL IDENTIFIER
IMCB04-E9
28
9: First alarm (De-energized alarm), second alarm (Energized alarm, Z-124 specification
provided)
10: First alarm (Energized alarm), second alarm (De-energized alarm, Z-124 specification
provided)
11: First alarm (De-energized alarm), second alarm (De-energized alarm, Z-124 specification
provided)
12: First alarm (Energized alarm, Z-124 specification provided), second alarm (Energized alarm,
Z-124 specification provided)
13: First alarm (De-energized alarm, Z-124 specification provided), second alarm (Energized
alarm, Z-124 specification provided)
14: First alarm (Energized alarm, Z-124 specification provided), second alarm (De-energized
alarm, Z-124 specification provided)
15: First alarm (De-energized alarm, Z-124 specification provided), second alarm (De-energized
alarm Z-124 specification provided)
Z-124 specification: This specification is for forcibly turning off the control output when the
burnout function is activated.
*5 0: Z-168 specification and Z-1018 specification not provided
1: Z-168 specification provided
2: Z-1018 specification provided
3: Z-168 specification and Z-1018 specification provided
4: Z-1041 specification (CT1 input value monitoring) provided
6: Z-1018 specification and Z-1041 specification (CT1 input value monitoring) provided
8: Z-1041 specification (CT2 input value monitoring) provided
10: Z-1018 specification and Z-1041 specification (CT2 input value monitoring) provided
12: Z-1041 specification (CT1 and CT2 input value monitoring) provided
14: Z-1018 specification and Z-1041 specification (CT1 and CT2 input value monitoring) provided
Do not set 5, 7, 9, 11 and 13. Malfunction may result.
Z-168 specification: Heater break alarm for three-phase heater specification.
Z-1018 specification: This specification is for displaying the STOP parameter symbol on the
SV display when operation stops (STOP).
Z-1041 specification: This specification can monitor the CT (current transformer) input
value regardless of types of control output (even if there is no heater
break alarm [HBA] ).