Rhein-Nadel Automation GmbH 23
VT-BA-ESR2000_EN_2023.docx
If a fault occurs during operation the controller switches itself off automatically and the display shows ER-
ROR and a brief message text blinking in alternate succession. The controller keeps this error message in
the memory even after disconnection from power supply until the message is reset in C009.
The output is above the admissible limit.
Check power input to the feeder and adjust, if necessary. Check frequency setting.
A short circuit occurred during operation.
Check cabling and magnets for damage.
The supply voltage is or was too high.
Check supply voltage. This error message is often caused by transient mains voltage peaks (e.g. by switch-
ing of inductive consumers). Install upstream filter, use other circuit, eliminate inductance, as necessary.
An inadmissibly high current peak occurred. Maybe the soft-start period is too short.
Response of the set cycle watchdog.
Remove the product flow malfunction.
Supply voltage is too low.
Check supply voltage.
Appears on the display briefly on power On and power Off.