Safety and regulatory information
R&S
®
Scope Rider RTH
9Getting Started 1326.1561.02 ─ 10
●
Do not use the instrument if the instrument casing, the display or any probe or
accessory are damaged. If you detect or suspect any damage, have the
instrument or accessory inspected by qualified service personnel.
●
Do not operate the instrument in wet, damp or explosive atmospheres. Make
sure that all connectors are completely dry before connecting the inputs.
●
Observe the operating conditions specified in the specifications document.
Measurement categories
IEC 61010-2-030 defines measurement categories that rate instruments on their
ability to resist short transient overvoltages that occur in addition to the working
voltage. Use the measurement setup only in electrical environments for which
they are rated.
●
0 - Instruments without rated measurement category
For measurements performed on circuits not directly connected to mains, for
example, electronics, circuits powered by batteries, and specially protected
secondary circuits. This measurement category is also known as CAT I.
●
CAT II:
For measurements performed on circuits directly connected to the low-voltage
installation by a standard socket outlet, for example, household appliances
and portable tools.
●
CAT III:
For measurements performed in the building installation, such as junction
boxes, circuit breakers, distribution boards, and equipment with permanent
connection to the fixed installation.
●
CAT IV:
For measurements performed at the source of the low-voltage installation,
such as electricity meters and primary overcurrent protection devices.