Operation
46 / 97
Preparation for start-up
7.2 Preparation for start-up
WARNING!
Potentially fatal injuries due to the engine taking in flammable gases!
Do not operate the engine in areas with a heavy concentration of
flammable vapors such as e. g. diesel, gas or propane.
When handling flammable liquids and gases, always shut off the
engine immediately.
The sequence of the described processes is to be maintained without ex-
ception!
Before each start-up it should be checked that all operating materials (oil
etc.) are full.
► Carry out complete visual checks.
► Check all relevant indicators and instruments for function and condi-
tion.
► Fill the fuel tank.
For further information, please refer to the chapter "Fuelling/refu-
elling".
► Check condition of suction screen fitted in the suction connection.
► Wear personal protection equipment.
For further information refer to Chapter "Servicing and cleaning".
7.2.1 Positioning the portable fire pump
► Ensure that the portable fire pump is stable.
► It must be ensured that no flammable materials are located in the vi-
cinity of the portable fire pump (wood, dry grass, etc.).
► While being operated, the portable fire pump may only be tilted a max-
imum of 35° in the direction of the suction inlet and operator, and 15°
in the direction of the radiator and exhaust.
► If the portable fire pump is placed on loose surfaces or if it is tilted
during operation, it must be secured against slipping and falling over.