Operation
48 / 97
Starting the engine
NOTICE
Unplanned event
The portable fire pump can be controlled at all times, even in critical
operating states (e.g. burst hose). The approach depends on the situation
and is the operator's responsibility.
Variety1:
► Press S16 a Idlefunction switch.
The speed of the portable fire pump is automatically reduced to
approx. 1700 min-1.
► Close screw-down valve (J10).
Engine cooling is maintained due to the water/air cooler..
Variety 2:
► Press the Engine shut down S59 function switch.
The portable fire pump is immediately shut down.
Engine cooling is interrupted by switching the engine off.
For safety reasons, the portable fire pump may only be operated with a
closed engine hood (MH1).
7.3.1 Switch on ignition
► Briefly actuate Engine start (S57) function switch.
► With (fully) switched off control panel, first the control panel will be
activated - display illuminates.
► With another brief press of a button, or with the control panel
switched on the ignition is activated.
7.3.2 Starten mittels Elektrostarter (Ausführung Armaturenbrett AR1)
With ignition switched on.
► Press the Engine start (S57) function switch, to start the engine, then
immediately release the switch.
Engine is running.
When the ignition is switched off.
► Actuate the Engine start (S57) function switch for approx. 5 seconds to
start the engine, then release the switch immediately.
Engine is running.