Operation
49 / 97
Starting the engine
NOTICE
Starting without control panel is switched on
For a shortened start procedure, by a continuous actuation (approx. 5 sec.)
of the Engine start function switch (S57) the portable fire pump can be put
into operation. The portable fire pump is then operated with a predefined
speed of 1700 min-1. A speed change can only be undertaken with a
control panel which with ready for operation.
Starting with defective control panel
Depending on the control panel defect, by a continuous actuation (approx.
5 sec.) of the Engine start function switch (S57) the portable fire pump can
be put into operation. The portable fire pump is then operated with a
predefined speed of 3500 min-1. A speed change cannot be undertaken in
this mode. Immediately rectify the fault, to ensure the safety and
operational readiness.
The max. permissible dry cycle time of the portable fire pump is 3 minutes.
After this time has expired info appears on the display screen (DB1) which
must be acknowledged with the middle function switch (EN1). Further op-
eration is the operator's responsibility and can lead to damage to the me-
chanical shaft seals.