Flush/drain
7.8 Flush/drain
A thorough flushing with seawater or dirty water is to be carried out after
each operation.
If seawater or dirty water was sucked up with the priming pump, it is import-
ant to rinse with clean water to prevent damage to the piston.
After rinsing, the entire portable fire pump must be drained.
Put the portable fire pump into operation and run at idle speed.
See "Starting the engine".
Feed pump with clean water or suck water from a clean water source.
Press the priming pump function switch (S3) for approx. 10 seconds .
Fully open the pressure valve(s) (J10) and rinse until clean water
comes out.
After completion of the rinsing process, drain the priming pump dry.
Actuate the priming pump function switch (S3) for one second.
The priming pump is sucked dry.
Drain the screw-down valves
Additionally, open the valves via the spindle limit (80).
Pull spindle limit (80) and open valves to the stopper.
The valves are fully open.
The water held inside is automatically expelled.
Re-close the valves.
The screw-down valves are drained.
When shutting down the portable fire pump after use, open the screw-down
valves half a revolution in order to relieve the seals.

Table of Contents