EasyManuals Logo

Rosenbauer FOX User Manual

Rosenbauer FOX
97 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #61 background imageLoading...
Page #61 background image
Operation
61 / 97
Fuelling and refuelling:
7.11 Fuelling and refuelling:
To perform a safe refuelling operation, it is essential to comply with all se-
curity measures.
WARNING!
Risk of fire and explosion!
When refuelling with a fuel canister, the filler neck must always be
used, after being securely locked onto the canister.
In all parts (canister and filler neck), it must be ensured that no damage
is present. In case of damage in the area of the fuel tank, the lining
around the filler neck or the air cooler (fan), refuelling during operation
is prohibited.
During refuelling, ensure that a deployable fire extinguisher (fire
classes A and B) is available. The minimum size of the fire extinguisher
must be 5 kg.
When the fuel tank cap is open, smoking is absolutely prohibited in the
vicinity of the portable fire pump. Fire and open flames are also
prohibited.
By spillage or overfilling of fuel during refuelling, an explosive
atmosphere in the area immediately around or above the puddle may
result.
CAUTION!
Environmental and health hazard due to fuel!
Fuels can create long-term water contamination, and endanger creatures
and plants of all kinds
Do not inhale fuel fumes.
Avoid skin contact with fuel.
Treat spilled fuel with a suitable desiccant and dispose of in an
environmentally sound manner.
NOTICE
Engine damage can be caused by incorrect fuel!
The portable fire pump can be fuelled only with premium petrol (min.
95 RON), E10 or Aspen four-stroke. Observe pictograms of the
portable fire pump.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rosenbauer FOX and is the answer not in the manual?

Rosenbauer FOX Specifications

General IconGeneral
Pump TypeCentrifugal
Max Pressure10 bar
TypePortable Fire Pump
Priming SystemAutomatic
Engine Type4-stroke petrol engine