Operation
56 / 89
Operation
► Briefly press the Stop power generator function switch to shut down
the power generator.
If the Stop power generator function switch is pressed for 5 sec-
onds the display is switched off.
If the Stop power generator function switch is pressed for 11 sec-
onds the control panel is switched off.
The power generator is switched off.
7.6.5 Refuel
To perform a safe refuelling operation, it is essential to comply with all safe-
ty measures.
WARNING!
Risk of fire and explosion!
The power generator may only be refueled during operation with the
aid of the external refuelling system. The external refuelling set and the
canister must be connected before starting.
Allow the power generator to cool down before opening the fuel tank
cover.
When refuelling with a fuel canister, the filler neck must always be
used, after being securely locked onto the canister.
In all parts (canister and filler neck), it must be ensured that there is no
damage. Refuelling is forbidden in the event of damage in the area of
the fuel tank, or the lining around the filler neck.
During refuelling, ensure that a deployable fire extinguisher (fire
classes A and B) is available. The minimum size of the fire extinguisher
must be 5 kg.
When the fuel tank cap is open, smoking is absolutely prohibited in the
immediate vicinity of the power generator. Fire and naked flames are
also prohibited.
By spillage or overfilling of fuel during refuelling, an explosive
atmosphere in the area immediately around or above the puddle may
result.
CAUTION!
Environmental and health hazard due to fuels!
Fuels can permanently pollute water bodies and endanger living organisms
and plants of all kinds
Do not inhale fuel fumes.
Avoid skin contact with fuel.
Treat spilled fuel with a suitable desiccant and dispose of in an
environmentally sound manner.