9
8.0 Storage
Rotork Fluid Systems actuators have been fully tested before
leaving the factory.
In order to keep the actuator in good condition
until installation, at least the following measures are
recommended:
Check presence and assembling of dust plugs
Keep the actuator on shipping pallet until installation
Never put the actuator directly on the ground.
Actuator must be positioned with the centre body cover
upwards
Protect the valve coupling area (adapter flange
and coupling joint, etc.) with rust preventive oil
e.g. Mobilarma LT or equivalent
Protect against weather action, covering the actuators
with appropriate polyethylene sheets
Check the actuator condition every 6 months and verify
the above protection measures remain in place
Remove package only at the installation time.
If long term storage is necessary, further operations must
be carried out to maintain the actuator in a good working
condition:
Replace the plastic plugs with metal plugs
Stroke the actuator every 12-months:
Cycle the actuator (using filtered, dehydrated air) to
the working pressure indicated on the name plate
Cycle the actuator with all the existing controls
(i.e. two complete strokes - one open, one closed)
at least 5 times
Cycle the actuator fitted with the mechanical manual
override or hydraulic manual override by means of the
override for 4 complete strokes
Disconnect the pneumatic and electric (if present) supply
from the actuator, and carefully close all the threaded
connections of the actuator
Remove electrical components covers (if present) to
ensure control terminals are clean and free from oxidation
and humidity. Reassemble the covers
In case of storage for over 12 months prior to installation,
it is recommended to operate the actuator to verify
correct operation
9.0 Long Term Storage
A4 US
US
A4
US
A4
A4 US

Other manuals for rotork gp series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the rotork gp series and is the answer not in the manual?

rotork gp series Specifications

General IconGeneral
EnclosureIP66
Communication ProtocolsFoundation Fieldbus
InputsDigital
OutputsDigital, Relay
DisplayLCD
Protection RatingIP66
Hazardous Area CertificationATEX, IECEx
Power Supply24 VDC, 115 VAC, 230 VAC

Related product manuals