Example 1 The default value of '15' (0000,1111 binary or 0F hex) makes all 4
inputs report closed contacts as true (1) and none of the inputs will
operate the actuator.
Example 2 The value 255 (1111,1111 binary or FF hex) makes all 4 inputs report
closed contacts as true (1) and all the inputs control the actuator in
their predefined way.
Example 3 The value 0 (0000,0000 binary or 00 hex) makes all 4 inputs report
open contacts as true (1) and none of the inputs will operate the
actuator.
7.1.12 ESD DI-4/Net Disable and Data Logger Disable (Parameter 14)
In the IQ/IQT/Skil/EH actuator this input determines the mode of operation for the ESD/DI-4 remote
input. The input can be used either to disable control of the actuator from the network, or to act as an
ESD/digital input. When this setting is made 'Active' the input will disable network control of the
actuator when the contact input is closed irrespective of the Aux Mask setting.
In addition the logging of torque and motor contactor starts count can be inhibited if the data logger is
turned off.