EasyManua.ls Logo

Saftronics FP5/GP5 Series - Page 97

Saftronics FP5/GP5 Series
108 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 12: Constant List
Firmware – S2011 and S3012
Revision: 1 (9/98) 89 © Saftronics, Inc.
Table 27 Constant List (Continued)
Constant Function Name Description
Factory
Setting
n109∗
Slip compensation gain
Unit: : 0.1%
Setting range : 0.0 to 9.9%
0.0%
n110∗
Motor no-load current
Unit: : 1%
Setting range : 0 to 99%
30%
n111∗
Primary delay time constant
Unit : 0.1 seconds
Setting range : 0.0 to 25.5 seconds
2.0 seconds
n112∗
Digital Operator connection fault
detection
0 : Connection fault detection is disabled
1 : Connection fault detection is enabled
0
n113∗
Frequency agree detection width
selection
Unit : 0.1Hz
Setting range : 0.0 to 25.5Hz
2.0Hz
n114∗
Function selection at LOCAL/REMOTE
switching
0 : At LOCAL/REMOTE switching, restart is enabled after stop
command is input.
1 : At LOCAL/REMOTE switching, restart is enabled at once.
0
n115∗
kVA selection
Unit : 1
Setting range :
GP5 (VSP2010): 0 to 8, 20 to 29
FP5 (VSP3010): 9 to F, 2A to 35
n116 CT/VT Selection
0 : Constant Torque
1 : VariableTorque
n117 Low Frequency OL Starting Point
Unit : 0.1Hz
Setting range : 0.0 to 10.0Hz
6.0Hz
n118 0Hz Continuous Operation level
Unit : 1%
Setting range : 25 to 100%
50%
∗ These constants are disabled for former softwares VSP1010 to VSP1015.
Enabled for the following software number (or after).
GP5 : VSP2010
FP5 : VSP3010
efesotomasyon.com - Control Techniques,emerson,saftronics -ac drive-servo motor

Table of Contents