Parameter name Parameter Values Description Default
Values
MAXIMUM SETPOINT MAX SETPOINT FOR HEATING
MAX SETPOINT FOR COOLING
This parameter allows to limit temperature setpoint range by
setting maximum setpoint for heating and cooling modes.
Default temperature setting range: 5,5⁰C - 40⁰C
35 ⁰C
VALVE PROTECTION ON
OFF
Valve protection function is intended to protect thermostatic
valves against getting stuck or jamming (e.g. in summer time
when heating system is disabled). If thermostat doesn’t send a
signal for heating for a period of 7 days, then heating is turned
on for a very short period of time just to move the actuators.
ON
INTERNAL RELAY DISABLE
ENABLE
RELAY TYPE NO-COM*
RELAY TYPE NC-COM*
If this option is disable then internal relay will not work at all.
If this option is enable then relay will goes on if thermostat is
calling for heating or cooling.
*parameter allows to set relay’s work mode
**as default the relay is disable, but if you use SQ610 as a
standalone device (device is not paired wirelessly with other
devices) the relay is enable
DISABLE**
MINIMUM TURN-OFF TIME MIN OFF TIME FOR HEATING
MIN OFF TIME FOR COOLING
This parameter species the minimum time between ON/OFF
switching in cooling mode. Thermostat have to wait this time
value before it switches on again.
Minimum Turn-O time range: 0 - 999
FOR
HEATING: 1
FOR
COOLING:
180
OPTIMISATION FEATURE OPTIMUM START ON / OFF
OPTIMUM STOP ON / OFF
Optimisation function is an energy-saving algorithm for eec
-
tive control of the heating device ensuring better temperature
comfort at pre-dened times of the day.
When the OPTIMUM START function is active, thermostats
sends the heating signal to the heat source earlier so that the
setpoint temperature is reached at the time dened in the
schedule.
When the OPTIMUM STOP function is active, thermostat takes
into account the system inertia, switches o the heat source
earlier to reach setpoint temperature at the time dened in the
schedule.
OPTIMUM
START: OFF
OPTIMUM
STOP: OFF
COMFORT WARM FLOOR DISABLE
LEVEL 1
LEVEL 2
LEVEL 3
This function helps to keep the oor warm, even if the room is
warm enough and there is no need to turn on the heating. User
can select 3 levels of warm oor feature.
PLEASE NOTE: it is not an economy feature, as your heating
system may be ON even if there is no heating demand from the
room thermostat. It is COMFORT feature which keeps your oor
warm all the time. It is only for Heating Mode.
DISABLE
mode
ONE TOUCH - this option is available only in ONLINE mode. In
this scenario S1/S2 input is used to work with volt-free contact.
By closing/opening S1/S2 contacts we can trigger any OneTouch
rule created in the Smart Home application. More information
in chapter 6.15
CHANGEOVER - an external volt-free contact is connected to
the S1/S2 input.
When S1/S2 contacts are closed, thermostat works in heating
mode.
When S1/S2 contacts are opened, thermostat works in cooling
mode.
This function is not available when thermostat is paired with
KL08RF wiring centre, TRV head or RX10RF receiver.
MINIMUM SETPOINT MIN SETPOINT FOR HEATING
MIN SETPOINT FOR COOLING
This parameter allows to limit temperature setpoint range by
setting minimum setpoint for heating and cooling modes.
Default temperature setting range: 5⁰C - 35⁰C
5 ⁰C