EB 8331-4 EN 65
Congurationlevel
− Invalidlimitsofprocessvariablerange(Codec88/c89):
The set point (Code c81) is within the range dened by the lower (Code c86) and upper
adjustment limits (Code c87). The lower limit of process variable range (Code c88) has a
greater value than the lower adjustment limit (Code c86) or the upper limit of process
variable range (Code c89) has a lower value than the upper adjustment limit (Code c87).
Recommendedaction: Adjust the limits of the process variable range (Code c88/c89) so
that they are identical to the adjustment limits (Code c86/c87) or that the adjustment lim-
its (Code c86/c87) are within the limits of the process variable range (Code c88/c89).
See Fig.22).
bar/%/°C
c81 Set point
c86 Lower adjustment limit
c87 Upper adjustment limit
c88 Lower limit of process variable range
c89 Upper limit of process variable range
Fig.22:Permissible adjustment limits and limits of process variable range (only for PID and POSF
applications)