106 EB 8389-1S EN
Appendix
Message Possible reasons Recommended action
Status
classication Single reset
Change in manipulated
variable range
The working range has shifted
towards CLOSED or max. OPEN
position.
Short-term change of
manipulated variable range
occurred.
Rethink the working range.
[ ]
u Sec. 6.2
Diagnostics > Monitoring
PST/FST status Status
(Code 84)
The partial stroke test or the full
stroke test has not been
completed successfully.
Read test status. See
section12/13.
[ ]
On/off valve (Code 85) The breakaway time or transit
time differs from the reference
value by the amount entered in
'Travel time assessment limit'.
The valve end position differs
from reference value by the
amount entered in 'Valve end
position limit'.
The valve end position cannot be
reached.
Check valve and actuator.
[ ]
u Sec. 5.3