EasyManua.ls Logo

Samson 3730 Series - Shipment and on-site transport; Accepting the delivered goods; Removing the packaging from the positioner; Transporting the positioner

Samson 3730 Series
120 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EB 8389-1S EN 37
On/off valve
5 On/off valve
The travel range of open/close (on/off) is
dened by the fail-safe position and the op-
erating point. As a result, the following pa-
rameters to determine the working range
and set point range are not analyzed and
cannot be changed.
Lower travel/angle range value
Upper travel/angle range value
Lower travel/angle limit
Upper limit for travel/angle
Lower set point range value
Upper set point range value
The discrete analysis of the reference vari-
able is performed in automatic mode.
If the set point ( ) is below 'Operating point
limit' when the automatic mode starts, the
valve (
) moves to the fail-safe position.
If
the set point increases and exceeds 'Operat-
ing point limit', the valve moves to the 'Op-
erating point'. The valve moves back to the
fail-safe position (0% in the example) if the
set point then falls below 'Fail-safe action
limit'.
Operating point
Operating point limit
Fail-safe action limit
Fail-safe position
t [s]
25
50
t > 6 s
x [%]
w [%]
If the set point ( ) is above 'Operating
point limit' when the automatic mode
starts, the valve (
) moves to the operating
point. The valve moves back to the fail-safe
position (0% in the example) if the set point
then falls below 'Fail-safe action limit'.
Operating point
Operating point limit
Fail-safe action limit
Fail-safe position
t <6s
t [s]
25
50
x [%]
w [%]
Starting the partial stroke test (PST)
A partial stroke test is started when the set
point ( ) moves in the range between 25
and 50% of the travel range and remains
there for longer than six seconds. See
uSection 12.1.
Operating point =
Fail-safe action limit
Fail-safe position
Operating point limit
Stop PSTStart PST
>
6
s
t [s]
w [%]
t
25
50

Table of Contents

Other manuals for Samson 3730 Series

Related product manuals