EB 8389-1S EN 95
Appendix
17 Appendix
17.1 Code list
Code
no.
Parameter – Readings/
values [default setting]
Description
Note: Codes with marked with an asterisk (*) must be enabled with Code3 prior to conguration.
48* Diagnostic parameters
d0 Temperature
Read only
Current operating temperature [°C] inside the positioner (accuracy
±3%)
d1 Min. temperature
Read only
Lowest temperature [°C] recorded inside the positioner since start-
ing the operating hours counter
d2 Max. temperature
Read only
Highest temperature [°C] recorded inside the positioner since start-
ing the operating hours counter
d3 No. of zero calibra-
tions
Read only
The number of zero calibrations performed since last initialization
d4 No. of initializations
Read only
Number of initializations performed since last start with default
values
d5* Zero limit
0.0 to 100.0%,
[5.0%] of the nominal
range, ESC
Valve position limit relating to nominal range
'Zero point' message (Code58) triggered depending on selected
status classication if limit is exceeded.
Note: The 'Zero point' message (Code58) has the default status
classication 'Maintenance required'. This classication can only
be changed in the operator software (e.g. TROVIS-VIEW).
d6 Condensed state
Read only
Summary of all status messages classied according to NAMUR
Recommendation NE107
OK: No message
C: Maintenance required
CR: Maintenance demanded
S: Out of specication
B: Failure
I: Function check
Appendix