68 EB 8389-1S EN
Course of end position
1.
Device settings > Positioner > Transfer
characteristic or Transfer characteristic on/
off
− Activate CLOSED end position (Code 14):
On
− CLOSED end position (Code 14):
0.0 to 49.9 %, [1.0 %]
2.
Device settings > Alarm settings
− Recording threshold:
0.10 to 5.00 %, [0.25 %]
3.
Device settings > Alarm settings > Status
classication > Valve position
Course of end position
− Monotonically increasing: [
], , ,
− Monotonically decreasing: [ ], , ,
− Alternating: [ ], , ,
10.1 Analysis and monitoring
A reference zero point must be recorded to
analyze the course of the end position. This
is recorded during the valve signature refer-
ence test (see u Section 4.1). In case a refer-
ence test has not been performed, the rst
zero point that the valve moved to serves as
the reference value. The reference value is
represented by a straight line in the course
of end position graph.
Note:
If the reference value has been reset
by selecting and executing "Reset
'Reference values for course of lower
end position" (see
u Section 2.1.1
),
the rst zero point that the valve
moves to after the reset serves as the
new reference value, provided it does
not exceed the 'Zero limit' (Code 48 -
d5).
If the analysis of course of the end position
pinpoints to a fault, the positioner generates
the 'Course of end position' message with
the selected status classication.
Diagnostics > Monitoring > Valve position
− Course of end position:
, , ,
10.2 Resetting single status mes-
sages
The 'Course of end position' message and
the measured data for the course of the end
position can be reset by selecting and exe-
cuting "Reset 'Course of lower end position".
If only the reference zero point is to be reset,
select and execute "Reset 'Reference values
for course of lower end position".
Diagnostics > Service/maintenance > Reset
− Reset 'Course of lower end position'
− Reset 'Reference values for course of lower end
position'