EasyManua.ls Logo

Samson 41-23 - Page 33

Samson 41-23
78 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EB 2512 EN 5-3
Installation
Correct!
Incorrect!
Connection at the top – incorrect position
Incorrect!
Connection at the side – optimal Connection at the bottom – incorrect position
Fig.5-2: Control line connection, depending on how the pipeline is routed
If the control line connection is located below
themiddleofthevalveinletange,arrange
the compensation chamber at the same level
astheinletange.Inthiscase,useapipe
whichisatleast½“insizeforthecontrol
line from the tapping point to the compensa-
tion chamber.
If the control line is connected above the
middleofthevalveinletange,installthe
compensation chamber at the same level as
the upstream pressure tapping point. The ad-
ditional pressure of the condensate head (H
k
,
Fig.5-3)mustbecompensatedforbyadjust-
ing the set point.
Needle valve
If the regulator tends to hunt, we recommend
installing a needle valve at the control line
connection (16) in addition to the standard
SAMSON screw joint with restriction.
Compensation chamber
A compensation chamber (18) is required
forliquidsabove150°Caswellasfor
steam. The mounting position of the compen-
sation chamber is indicated by an adhesive
label on the chamber itself as well as by an
arrow and the word "top" stamped on the
top of the chamber.
Thismountingpositionmustbeadheredto;
otherwise the safe functioning of the regula-
tor cannot be guaranteed.
Weld the line coming from the pressure tap-
ping point to the
3
/
8
pipe socket on the
chamber.
Install the compensation chamber at the
highest point of the pipeline. Consequently,
the control line between compensation
chamber and actuator must also be installed
with a downward slope. In this case, use a
3
/
8
pipewithscrewttings.

Table of Contents

Related product manuals