4.4 D-Register Explanation
D-Register is group of data which can use with communication all of TEMI880’s condition.
Each group has 100 registers and these are classified as follows.
D-Register Range Group Name Description Read Write
D0001~D0099 PROCESS Basic process display X
D0100~D0199 FUNCTION Operation information display
D0200~D0299 RESERVATION Time & Reservation
D0300~D0399 ON OFF / IS ON/OFF & Inner signal
D0400~D0499 ALARM / TS Alarm & Time signal
D0500~D0599 TEMP PID Temp. P.I.D
D0600~D0699 HUMI PID Humi. P.I.D
D0700~D0799 COMM Communication X
D0800~D0899 OUTPUT Output
D0900~D0999 INPUT Input
D1000~D1099 PROGRAM Program
D1100~D1199 RESERVED Blank X X
D1200~D1299 RESERVED Blank X X
D1300~D1399 FILE1 Display Temp. TSP of segment X
D1400~D1499 FILE2 Display Humi. TSP of segment X
D1500~D1599 FILE3 Display setting time of segment X
D1600~D1699 PROG_INFO Basic information of program pattern
D1700~D1799 FILE4 Set TS1 of segment X
D1800~D1899 FILE5 Set TS2 of segment X
D1900~D1999 FILE6 Set TS3 of segment X
D2000~D2099 FILE7 Set TS4 of segment X
D2100~D2399 RESERVED Blank X X
Each D-Register is consisted of hexadecimal 4 characters(2-Byte).