4th Edition of TEMI880 IM : Jan. 29. 2007 Page 46 / 119
WAIT ZONE : Temperature TEMP ZONE, Humidity HUMI ZONE.
1 A case where wait release within Wait Time
2 A case where PV does not enter WZ(Wait Zone) within Wait Time
The relation of the wait operation and wait time
WAIT TIME
SP
WAIT ZONE
WAIT ZONE
PV
segment n
segment (n+1)
segment (n+2)
wait operation
(time stop)
The point of the wait release
process segment (n+1)
WAIT TIME
SP
WAIT ZONE
WAIT ZONE
PV
segment n
segment (n+1)
segment (n+2)
wait operation(time stop)
The point of the wait release
process segment (n+1)