SINUS MINI High performance Vector Control Inverter User Manual
40
24800BPS
39600BPS
419200BPS
538400BPS
FC.01
Data format
0: 8,N,2 for RTU MODBUS
1: 8,E,1 for RTU MODBUS
2: 8,O,1 for RTU MODBUS
3: 7,N,2 for ASCII (MODBUS
4: 7,E,1 for ASCIIMODBUS
5: 7,O,1 for ASCIIMODBUS
6 8,N,1 free communication format
78,E,1 free communication format
8 8,O,1 free communication format
9Host mode, send current running frequency
0
+
FC.02
Local address
1~320 is the broadcast address
1
+
FC.03
Communication
timeout detect
0 No detection
2.0~10.0s
0
+
FC.04
Response delay
2~1000ms
+
FC.05
EEROM Store
selection
0Store
1no store function
0
+
FD.00
Motor overload
protection mode
0: No protection
1: Common motor protection
2: Variable frequency motor protection
1
+
FD.01
Motor overload
protection factor
20.0~150.0%
100.0
+
FD.02
Over voltage stall
selection
0: Disabled
1: Enabled
1
+
FD.03
Stall over voltage
point
115.0~150.0%UDC
120.0
+
FD.04
Selection of
overload pre-alarm
0: Detect at constant speed and alarm
1: Detect all the time and alarm
0
+