SINUS MINI High performance Vector Control Inverter User Manual
41
detection
FD.05
Overload detection
threshold
20.0~180.0%(Ie)
150.0
+
FD.06
Overload
pre-alarm delay
0.0~60.0s
2.0
+
FD.07
Auto current
limiting threshold
20.0~180.0%
150.0
+
FD.08
Frequency
decrease rate
during current
limiting
0.00~99.99Hz/s
0.00
+
FD.09
Action mode of
auto current
limiting
0: Disabled
1: Enabled during Acc/Dec, disabled at constant
speed
2: Enabled during Acc/Dec, enabled at constant
speed
1
+
FD.10
Auto reset
0:Disabled
1~5:Times of fault reset
0
+
FD.11
Auto reset interval
2.0~20.0s
2.0
+
FD.12
Relay action in
Auto reset
0:No action
1:action
0
FD.13
Act selection at
under voltage fault
0:No action
1:Act in running state
2:Act in running and stop state
1
+
FD.14
reserved
1
+
FD.15
reserved
1
+
FD.16
Under Voltage
Point
380V:250-440
220V:200-260
380V:400
220V:250
+
FD.17
reserved
+
FD.18
reserved
+