The communication of terminal 485
is faulty
Check whether the data receiving
and transmission complies with
the protocol, whether the check
sum is correct and whether the
receiving and transmission
interval complies with the
requirements
The communication of terminal 485
is time-out
Check whether the
communication timeout is set
properly and confirm the
communication cycle of the
application program
The failure alarm parameter is set
improperly
Adjust the failure alarm parameter
Analog close loop
feedback failure
Analog close loop
feedback failure
Improper setting of FA parameter
group;
Modify setting of FA parameter
group;
Improper setting of motor
parameters;
Re-set the motor’s rated
parameters;
Significant deviation of parameters
obtained after tuning comparing with
the standard parameters;
Execute motor auto-tuning again
under zero load condition.
Current detection
failure
Current sensor failure and bad
contact
Act trigger by external fault
Check external device according
external fault signal
1. refer to OL1 and OL2;
2. Improper setting of FD.04~FD.06
1. refer to OL1 and OL2;
2. Modify setting of FD.04~FD.06