SATEL MICRA 19
5. OUTPUT ON 1 – violation of the zone will activate the output 1, if the output is of the
CONTROLLED type.
6. OUTPUT ON 2 – violation of the zone will activate the output 2, if the output is of the
CONTROLLED type.
7. OUT 1 ON (TIME) – violation of the zone will activate the output 1 for a preset cut-off
time, if the output is of the CONTROLLED type.
8. OUT 2 ON (TIME) – violation of the zone will activate the output 2 for a preset cut-off
time, if the output is of the CONTROLLED type.
9. OUTPUT OFF 1 – violation of the zone will deactivate the output 1, if the output is of the
CONTROLLED type.
10. OUTPUT OFF 2 – violation of the zone will deactivate the output 2, if the output is of
the CONTROLLED type.
L threshold – the lower voltage threshold for analog zone. If the voltage drops below the
defined value (minus tolerance), the module will register zone violation. Entering value 0
means that the voltage threshold is not controlled.
H threshold – the upper voltage threshold for analog zone. If the voltage rises above the
defined value (plus tolerance), the module will register zone violation. Entering value 0
means that the voltage threshold is not controlled. The maximum value that can be
programmed is 16.56 V.
Tolerance – the voltage value to be subtracted from the defined value at threshold L when
the voltage drops below threshold L or added to the defined value at threshold H when
the voltage rises above threshold H so that the module can register exceeding the
programmed value / the voltage value to be added to the defined value at threshold L
when the voltage rises above threshold L or subtracted from the defined value at
threshold H when the voltage drops below threshold H so that the module can register
zone restore. The field is available to analog zones.
Output 1 / 2 – fields available for the communication device mode. They allow you to
define, if and how the zone will control the output. Click on the field twice to display
successively:
– blank field – zone does not control the output,
– ON – violation of the zone or exceeding the voltage value at threshold L or H, as
defined for the zone, will activate the output,
– ON for time – violation of the zone or exceeding the voltage value at threshold L or H,
as defined for the zone, will activate the output for a defined time (cut-off time must
be defined for the output),
– OFF – violation of the zone or exceeding the voltage value at threshold L or H will
deactivate the output.
Wireless zones
Name – individual name of a wireless zone (up to 16 characters).
Type – information on the type of wireless device:
0: no;
1: MMD-300 (magnetic contact);
2: MPD-300 (PIR);
3: MSD-300 (smoke and heat detector).
Serial number – displayed in the field is the detector serial number.
Note: After the detector is added to the system and its serial number is displayed in the
corresponding field, it is advisable to check it with the detector serial number.