EN 50559
This thermostat complies with EN 50559 (VDE 0705-559) for electrical floor heating.
The regulation applies to electrical floor heating, with a maximum floor weight of 4
kN/m². To ensure that hotspots due to unintentionally covering up the surface are
avoided, the heating function can be time-limited as per EN/DIN.
Note that this function is not applicable to other heating applications such as wall
and/or ceiling heating
If it can be foreseen in advance that unintentional covering up of a floor might occur,
then it is important to assess the correct period of time for which the floor heating
must be time-limited.
The heating can be limited using a set number between 0 - 20 minutes per hour.
1. Tap the “Menu” button on the home screen.
2. Then tap the “Engineer Settings” button.
3. Scroll down and tap the “EN 50559” button.
4. Use the “Up Arrow” or “Down Arrow” button to set the number of minutes - the
thermostat should not heat per hour.
5. Confirm the value with “√”.
6. The thermostat will automatically return to “Engineer Settings”.
Mon 11:15
17:00
23.5
°
Manual Other...
1
Heating Schedule
Energy Use
User Settings
Engineer Settings
Heating Schedule
Energy Use
User Settings
Engineer Settings
Heating Schedule
Energy Use
User Settings
Engineer Settings
Sensor Application
Adaptive Function
Open Window
Factory Reset
Temp. Scale
Room Sens. Calibr.
Floor Sens. Calibr.
Sensor Type
Sensor Application
Adaptive Function
Open Window
Room Sens. Calibr.
Floor Sens. Calibr.
Sensor Type
Sensor Application
Adaptive Function
Open Window
Factory Reset
Temp. Scale
Room Sens. Calibr.
Floor Sens. Calibr.
Sensor Type
Mon 11:15
17:00
23.5
°
Manual Other...
1