LEROY-SOMER
7
2010.11 / f
Installation and maintenance
R438
A.V.R.
- LAM : action eliminated by cutting the ST5
jumper.
2.3.2 - Gradual voltage return function
During load impacts, the function helps the
genset to return to its rated speed faster
thanks to a gradual increase in voltage ac-
cording to the principle:
- If the speed drops between 46 and 50 Hz,
the rated voltage follows a fast gradient as it
is restored.
- If the speed drops below 46 Hz, since the
engine needs more help, the voltage follows
a slow gradient as it returns to the reference
value.
2.4 - Typical effects of the LAM with
a diesel engine with or without a
LAM (U/F only)
2.4.1 - Voltage
2.4.2 - Frequency
2.4.3 - Power