PACKAGING/STORAGE:
 GenCOOL PC -26 is supplied in 210 l metallic barrels with smooth interior linings.
 It can be stored for 2 years in its original container and packaging.
 Avoid zinc coated containers.
RECOMMENDATIONS FOR USE:
 Compatible with the original fluid.
 It is recommended that the cooling system is completely drained when replacing the fluid.
SPECIFICATIONS UNITS SPECIFIED VALUES
TRIAL
METHODS
Density at 20°C
kg/m
3
1,059 +/- 3
R 15-602-1
pH
pH
7.5 to 8.5
NF T 78-103
Alkalinity reserve
ml
>=10
NF T 78-101
Boiling point
°C
105 +/- 2
R 15-602-4
Freezing point:
°C
-26 +/- 2
NF T 78-102
Glassware corrosion :
(test with antifreeze)
mg/test piece
R 15-602-7
- Copper
+/- 2.6
- Weld
+/- 0.5
- Brass
+/- 2.3
- Steel
+/- 1.6
- Cast iron
+/- 0.8
- Cast aluminium
+/- 1.0
Corrosion on warm plate
(test with antifreeze)
mg/(cm²week)
+/- 0.17
R 15-602-8
3. Installation-Connections
3.1. Unloading
3.1.1 Safety during unloading
To unload electrical generating sets from their transport supports with optimum safety and efficiency, you must ensure that the
following points are observed:
- The lifting machinery or equipment is suitable for the work required.
- The sling is correctly positioned in the central lifting eye or the lifting arms are correctly positioned in the fork-lift pockets intended
for this purpose.
- The ground is able to bear the load of the generating set and its lifting machinery without stress (otherwise lay down stabilising
beams of sufficient strength).
- The generating set is put down as close as possible to its place of use or transport, in a clear space with free access.
Example of equipment to be used:
 crane, slings, lifting beam, safety hook, shackles.
 Forklift truck.