3.4.3 Power connections
Disconnect the battery leads or use the battery isolating switch before carrying out any operations
on the generating set.
(To disconnect the battery, disconnect the negative lead (-) first).
Warning
1. Open the access hatch to the power section.
2. Feed the power cables through the access hatch on the genset control unit.
3. Connect the power cables to the bars. (N/L0-L1-L2-L3 or N2-R2-S2-T2).
4. Connect the power cables to the installation ensuring the live and neutral wires are correctly connected.
Ensure that the direction of rotation of the phases is identical on the genset and the installation.
(Our gensets are factory-set with a conventional direction of phase rotation)
Warning
N/L0
or
N2
L
3
or
T2
L2
or
S2
L
1
or
R2
USE
Acces hatch