IG>> . tChar [Protection Para / IG>>]
0.1 0.05 . . . 10.00 P.1
Time multiplier/tripping characteristic factor. The setting range depends on the selected tripping curve.
IG>> . tMin [Protection Para / IG>>]
0.00s 0.00s . . . 20.00s P.1
Minimum trip delay time. Independent of the measured current values, the trip delay time does never fall below the
minimum that is set here.
IG>> . Reset Mode [Protection Para / IG>>]
instantaneous instantaneous, denite time, inverse time
╚═▷ Reset Mode
P.1
Reset Mode
IG>> . tReset [Protection Para / IG>>]
0.1s
Only available if:
• IG>> . Reset Mode = denite time•
0.00s . . . 60.00s P.1
Reset delay for intermittent phase failures (INV characteristics only)
IG>> . IH2 Blo [Protection Para / IG>>]
Inactive, Active
╚═▷ Mode
P.1
Blocking the trip command, if an inrush is detected.
IG>> . ExBlo [Protection Para / IG>>]
“-” “-” . . . Prot . Pos OFF
╚═▷
P.1
External blocking of the module if the state of the assigned signal is true.
7.11.3
IG>>: Input States
IG>> . ExBlo-I [Operation / Status Display / IG>>]
Module input state: External blocking
51WIC1WIC1-1.0-EN-REF
7 Protection Parameter
7.11.3 IG>>: Input States