• ╚═▷ I2/I1> . Denition•
• [ . . . ]•
Denition Description
Trip The function operates as a protection function, i.e. trips the breaker in case of a fault.
Alarm The function operates as a supervision function, i.e. a fault generates neither alarm nor
trip, but an »Alarm« signal gets issued instead.
Out. Mode
Select whether the output shall operate as an impulse output (for connecting a ag indicator
with full compatibility to the 1st generation WIC1), or as a relay output (with a xed,
pre-dened usage as a self-supervision contact). \n(The usage as a self-supervision contact
is only possible with an externally supplied WIC1-4, and connecting a ag indicator is not
permissible with this setting.)
Selection list referenced by the following parameters:
• ╚═▷ Prot . Out. Mode•
Out. Mode Description
Impulse Output The output shall operate as an impulse output (for connecting a ag indicator with full
compatibility to the 1st generation WIC1).
Syst. O.K. & Ext.Suppl. The output shall operate as as a self-supervision output, together with an external
output relay. (See the User Manual chapter “Technical Data” for the specication of a
compatible output relay).
The signal at this output indicates that the WIC1 is running and is supplied by external
auxiliary power and has loaded sucient electrical energy for triggering the trip impulse
output.
Relay Output The output shall operate as as a relay output (for connecting an output relay).
Selection list referenced by the following parameters:
• ╚═▷ DiggiMEC . FI / BO 1 assign.•
• ╚═▷ DiggiMEC . FI / BO 2 assign.•
•
╚═▷ DiggiMEC . FI / BO 3 assign.
•
• ╚═▷ DiggiMEC . LED2 assign.•
• ╚═▷ DiggiMEC . LED3 assign.•
• ╚═▷ Prot . Out. assign.•
• [ . . . ]•
129WIC1WIC1-2.0-EN-REF
13 Selection Lists