M4200 - User manual
Revision: 07.03.2017 Page 19
General settings
Before programming the general settings please select the position number on the rotary switch (position 9).
In the table below the default settings are marked with bold type.
Switch row 1
Function
Switch setting
Description
Alarm Relay 1
SW 1.1
OFF
Normally De-energized
ON
Nomally Energized
Alarm Relay 2
SW 1.2
OFF
Normally De-energized
ON
Nomally Energized
Siren Relay
SW 1.3
OFF
Normally De-energized
ON
Nomally Energized
Open Collector 1
SW 1.4
OFF
Normally De-energized
ON
Normally low
Open Collector 2
SW 1.5
OFF
Normally De-energized
ON
Normally low
Open Collector 3
SW 1.6
OFF
Normally De-energized
ON
Normally low
Open Collector 4
SW 1.7
OFF
Normally De-energized
ON
Normally low
Spare
SW 1.8
OFF
No effect
ON
No effect