EasyManua.ls Logo

Selco M4200 - Multiple Units; Synchronisation

Selco M4200
35 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
M4200 - User manual
Revision: 07.03.2017 Page 5
Installation instructions
This section contains information about how to install the alarm monitor.
Single unit
Figure 2 shows the default connection of the input and output terminals on the alarm monitor. Input terminals
1 - 8 are connected to +REF OUT (positive supply) via potential free contacts.
Reset, test and block terminals are connected to GND via potential free contacts.
Lamps are connected to the outputs; the lamps are supplied from same source as the unit. Terminal 26 is
connected to ÷ (negative supply).
Figure 2. Wiring example, single unit (default connection).

Table of Contents