- 35 -
Ŷ Analog output (option)
Ɣ Number of output points : 1
Ɣ Type of analog output : Selectable from measured value, target value (SV in execution) and control output
Ɣ Output specification/rating : Current 4 - 20mA DC (Maximum load resistance 300 ) Voltage 0 - 10V DC (Maximum load
resistance 2mA) 0 - 10mV DC (Output resistance 10 )
Ɣ Output accuracy : ±0.3% FS (Comprehensive accuracy when measured value is output ±0.6% FS )
Ɣ Scaling : Within measuring range or output range (inversed scaling possible)
Ɣ Output resolution : About 1/10000
Ɣ Output updating cycle : 0.25 second
Ɣ Isolation : Not insulated from P.I.V. control output but insulated from others
Ŷ Status output (DO) (option)
Ɣ Number of output points : 4
Ɣ Type of output : None, scaleover, hold, guarantee soak, time signal (2 types), RUN status, step signal, end signal, FIX
Ɣ Output specification/rating : Open collector darlington output, voltage 24V DC (maximum load current 20mA), saturation voltage
during status output ON 1.2V
Ɣ Output updating cycle : 0.25 second
Ɣ Isolation : Insulated from other inputs and outputs
Ŷ Program
Ɣ Number of patterns : Maximum 4 (setting 1, 2 or 4 possible)
Ɣ Number of steps : Maximum 10 - 40 (Total number of steps = 40)
Ɣ Number of PID types : Maximum 6
Ɣ Number of zone PID types : Maximum 3
Ɣ Zone hysteresis : 0 - 999 digits
Ɣ Time setting : 0 hour 0 minute - 99 hours 59 minutes or 0 minute 0 second - 99 minutes 59 seconds/1 step
Ɣ Setting resolution : 1 minute or 1 second
Ɣ Accuracy of time : ± (set time × 0.02% + 0.25 second)
Ɣ Setting for each step : SV, step time and PID No.
Ɣ Time signal : 2 outputs/pattern, to be set within time setting range
Ɣ Number of pattern executions : Maximum 9999
Ɣ PV start : ON/OFF
Ɣ Guarantee soak : OFF, 1 - 999 digits
Ɣ Hold : Front key input or external control input
Ɣ Advance : Front key input or external control input
Ɣ Power failure compensation : ON/OFF (guarantee not applicable to the period of time of step in which power failure occurs)
Ŷ General specification
Ɣ Data storage : Non-volatile memory (EEPROM)
Ɣ Environmental conditions for instrument operation:
Temperature : –10 – 50 ˚C
Humidity : 90% RH or less (no dew condensation)
Height : 2000m from the sea level or lower
Category : II
Degree of pollution
Ɣ Storage temperature
Ɣ Supply voltage
:
2
: –20 – 65 ˚C
: 100 - 240V AC±10% 50/60Hz
24V AC/DC±10% (option)
Ɣ Input/noise removal ratio : 50 dB or higher in normal mode (50/60 Hz)
130 dB or higher in common mode (50/60 Hz)
Ɣ Insulation resistance : Between input/output terminals and power terminal 500V DC 20 M or above
Between input/output terminals and protective conductor terminal 500 V DC 20 M or above
Ɣ Dielectric strength : Between input/output terminals and power terminal 3000 V AC/minute
Between power terminal and protective conductor terminal 1500V AC/minute
Ɣ Power consumption : 16VA maximum for AC, 7 W for DC
Ɣ Conformity with standards
Safety : IEC61010-1 and EN61010-1
IEC61010-2-030 and EN61010-2-030
EMC : EN61326-1
Ɣ Protective structure : Only front panel has dust-proof and drip-proof structure equivalent to IP66. (Panel thickness :1.2-3.2mm)
Ɣ Material of case : PPE(equivalent to UL94V-1)
Ɣ External dimensions : H96 × W96 × D111mm (Panel depth: 100mm)
Ɣ Panel thickness : 1.0 - 4.0mm
Ɣ Mounting dimensions : H92 × W92mm