- 34 -
Output limiter : Lower limit 0.0 - 99.9%, higher limit 0.1 - 100.0%
Proportional cycle : 1 - 120 seconds (when contact and SSR drive voltage output)
Manual control : 0.0 - 100.0% Setting resolution 0.1
Ɣ Control output characteristic : RA/DA to be set by front key
Ɣ Isolation : Contact output insulated from all
AO (analog output) not insulated from SSR drive voltage, current or voltage output but insulated
from others
Ŷ External control input (DI)
Ɣ Number of input points : 4
Ɣ Type of input : Edge or level input (none, RUN/RST, HLD, ADV, FIX and start pattern No.)
DI1 fixed to RUN/RST for DI2 - 4, selectable from none, RUN/RST, HLD, ADV, FIX and start
pattern No.
Ɣ Input rating : Voltage 5V DC (0.5mA/1 input)
Ɣ Input holding time : Minimum 0.125 seconds
Ɣ Isolation : Not insulated from input and system but insulated from others.
Ɣ Action input : No-voltage contact or open collector
Ŷ Event output
Ɣ Contact output rating : Normal open (1a x 3 common) 240V AC 1A (resistive load)
Ɣ Action : ON-OFF action
Ɣ Hysteresis : 1 - 999 digits (during alarm output)
Ɣ Types : Selectable from the following 16 types respectively for EV1, EV2 and EV3
No selection, Higher limit deviation, Lower limit deviation, Outside higher/lower limit deviations,
Within higher/lower limit deviations, Higher limit absolute value, Lower limit absolute value,
Scaleover, Hold, Guarantee soak, Time signal (2 types), RUN status, step signal, End signal, FIX
Ɣ Event setting range
Absolute value alarm : Within measuring range
Deviation alarm : Higher limit deviation –1999 - 2000 digits, lower limit deviation –1999 - 2000 digits
Outside higher/lower limit deviations: 0 - 2000 digits
Within higher/lower limit deviations : 0 - 2000 digits
Ɣ Standby action : Selectable from the following 4 types respectively for EV1, EV2 and EV3
: None, Standby 1 (standby only when power is applied), Standby 2 (standby when power is applied,
when SV in execution is changed, or when switching RST to RUN) and Standby 3
(input abnormality not output [Control mode])
Ɣ Output updating cycle : 0.25 second
Ɣ Isolation : Insulated from other inputs
Ŷ Communication function (option)
Ɣ Type of communication : RS-232C or RS-485
Ɣ Communication system : RS-232C/3-line type half duplex system, RS-485/2-line type half duplex multi-drop (bus) system
Ɣ Synchronization system : Start-stop synchronization system
Ɣ Communication distance : RS-232C/Max. 15m, RS-485/Max. 500 m (depending on conditions)
Ɣ Communication address : 1 – 255
Ɣ Communication speed : 1200, 2400, 4800, 9600, 19200 bps
Ɣ Communication delay : 1 - 100 (0.512msec/unit)
Ɣ Communication memory mode : Selectable from EEP, rAm and r_E
Ɣ Communication protocol : Shimaden standard mode
Data format : 7E1, 7E2, 7N1, 7N2, 8E1, 8E2, 8N1, 8N2
Control code
: STX_ETX_CR, STX_ETX_CRLF, @_:_CR
Checksum (BCC) : Add, Add two's cmp, XOR, None
Communication data : ASCII data
: MODBUS ASCII mode
Data format : 7E1, 7E2, 7N1, 7N2
Control code : CRLF
Checksum (BCC) : LRC check
Communication data : ASCII data
Function code
: 03H, 06H
1)03H Reading of data
2)06H Writing of data
: MODBUS RTU mode
Data format : 8E1, 8E2, 8N1, 8N2
Control code : NON
Checksum (BCC) : CRC-16
Communication data : Binary data
Function code : 03H, 06H
1)03H Reading of data
2)06H Writing of data
Ɣ Communication mode type : Selectable from COM1 and COM2.
Ɣ Number of connectable instruments : 1 for RS-232C, 31 for RS-485 (Address setting 1 - 255)
Ɣ
Isolation : insulated from other inputs and outputs
Ɣ Others : Start character and BCC operation method also selectable