EasyManuals Logo

Shinko BCS2R Series User Manual

Shinko BCS2R Series
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #23 background imageLoading...
Page #23 background image
23
9. Troubleshooting
If any malfunctions occur, refer to the following items after checking the power supply to the controller.
9.1 Indication
Problem Presumed cause and solution
is indicated in the PV
Display.
The controller is in the EXCEEDED indicator lighting duration time
mode.
Press the key twice to revert to the PV/SV Display Mode.
or is
indicated in the PV Display.
Maximum (Minimum) value is indicated.
Press the key once to revert to the PV/SV Display Mode.
is flashing in the PV
Display.
Burnout of thermocouple, RTD or disconnection of DC voltage (0 to
1V DC)
Replace each sensor.
How to check whether the sensor is burnt out
[Thermocouple]
If the input terminals of the instrument are shorted, and if a value
around room temperature is indicated, the instrument is likely to
be operating normally, however, the sensor may be burnt out.
[RTD]
If approx. 100 of resistance is connected to the input terminals
between A-B of the instrument and between B-B is shorted, and
if approximate 0 (32 ) is indicated, the instrument is likely to
be operating normally, however, the sensor may be burnt out.
[DC voltage (0 to 1 V DC)]
If the input terminals of the instrument are shorted, and if a scaling
low limit value is indicated, the instrument is likely to be operating
normally, however, the signal wire may be disconnected.
Check whether the input terminals of thermocouple, RTD or DC voltage
(0 to 1 V DC) are securely mounted to the instrument input terminal.
Connect the sensor terminals to the instrument input terminals securely.
is flashing in the PV
Display.
Check whether input signal source for DC voltage (1 to 5 V DC) or
Direct current (4 to 20 mA DC) is disconnected.
How to check whether the input signal wire is disconnected
[DC voltage (1 to 5 V DC)]
If the input to the input terminals of the instrument is 1 V DC and
if a scaling low limit value is indicated, the instrument is likely to be
operating normally, however, the signal wire may be disconnected.
[Direct current (4 to 20 mA DC)]
If the input to the input terminals of the instrument is 4 mA DC and
if a scaling low limit value is indicated, the instrument is likely to be
operating normally, however, the signal wire may be disconnected.
Check whether input signal wire for DC voltage (1 to 5 V DC) or Direct
current (4 to 20 mA DC) is securely connected to the instrument input
terminals.
Check if polarity of thermocouple or compensating lead wire is correct.
Check whether codes (A, B, B) of RTD agree with the instrument terminals.
The indication of PV Display is
abnormal or unstable.
Check whether sensor input or temperature unit ( or ) is correct.
Select the sensor input and temperature unit ( or ) properly.
Sensor correcting value is not suitable. Set it to a suitable value.
Check whether the specification of the sensor is correct.
AC leaks into the sensor circuit. Use an ungrounded type sensor.
There may be equipment that interferes with or makes noise near
the controller.
Keep equipment that interferes with or makes noise away from the
controller.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Shinko BCS2R Series and is the answer not in the manual?

Shinko BCS2R Series Specifications

General IconGeneral
BrandShinko
ModelBCS2R Series
CategoryController
LanguageEnglish

Related product manuals