21
[Automatic cold junction temperature compensation] (Only thermocouple input type)
This detects the temperature at the connecting terminal between the thermocouple and the instrument,
and always maintains at the same status as if the reference junction location temperature was at 0
(32 ).
[Power failure countermeasure]
The setting data is backed up in the non-volatile IC memory.
[Warm-up indication]
After the power supply to the instrument is turned on, the PV Display indicates an input type, and SV
Display indicates input range high limit value (for thermocouple, RTD inputs) or scaling high limit
value (for Direct current and voltage inputs) for approximately 3 seconds, and control output is turned
OFF.
[Peak (or Bottom) value hold function]
While the EXCEEDED indicator is lit, the peak value is maintained during high limit action, or
Bottom (the lowest) value is maintained during low limit action.
Present measured value will be initialized after reset using the key or the external reset
input function.
[EXCEEDED indicator lighting duration time]
EXCEEDED indicator lighting time can be measured and indicated by pressing the Mode ( ) key
in the PV/SV Display Mode.
Measurement range: 0:00 to 99:59 (Hour:Minute, Minute:Second)
Lighting time will be initialized to 0:00 after reset using the key or the external reset input
function.
Accessories included: Mounting frame: 1 piece
Instruction manual: 1 copy
Accessories sold separately: Terminal cover