2 SPECIFICATIONS
2.4 Performance Specifications
31
2
Test outputs of an FX5-SF-MU4T5
*1 A cross-circuit detection is performed only in the module.
*2 All the output current in a system is limited. Observe the following limit values.
Supply current for all sensors connected to an FX5-SF-MU4T5 (T0/T1) and FX5-SF-8DI4 (T0 to T7): I < 600 mA
Safety outputs of an FX5-SF-MU4T5
*1 A cross-circuit detection is performed only in the module.
*2 A response time without any sensors. When sensors are connected, the data of the connected sensors is applied and the minimum
switch-off time is extended.
Item Specification
Number of outputs 2 points
Output method Source output, short-circuit protection, cross-circuit detection
*1
Output voltage 16 VDC to 30 VDC
Output current
*2
120 mA
Test cycle (T0 and T1) Program 1, 2, 4, 5, 6, and 9 40 ms
Program 3.2 T0 = 400 ms
T1 = 40 ms
Item Specification
Number of outputs 4 points
Output method Source output, short-circuit protection, cross-circuit detection
*1
Output voltage 18.4 VDC to 30.0 VDC
Switching current 2.0A( T
A
45)
1.5A( T
A
55)
Total current I
sum
4.0A( T
A
45)
3.0A( T
A
55)
Leak current (in the switch OFF status) 1 mA or less
Indication of output operation LED lights when an output is ON.
Response time
*2
(I0/I1) Program 1, 2, 4, 5, 6, and 9 29 ms
Program 3.1, 7, and 8 9 ms
Program 3.2 81 ms/29 ms
Response time
*2
(I2/I3) Program 4, 5, and 6 29 ms
Program 1, 2, 3, 7, 8, and 9 9 ms
Response time (XS0) 9 ms
Off delay time 0 / 0.5 / 1 /1.5 / 2 / 2.5 / 3 / 3.5 / 4 / 5 s
@
@
@
@