36
2 SPECIFICATIONS
2.6 Parts Names
FX5-SF-8DI4
The following shows the indications of the LEDs on an FX5-SF-8DI4.
*1 The ERROR LED flashes rapidly and repeatedly at regular intervals.
LED name LED color Description
POWER Green Indicates the power supply status.
ON: Normal operation
Flashing: The rotary switch setting was changed during operation.
OFF: Powered OFF
ERROR
*1
Red Indicates an error status.
ON: An error occurred in any one of the safety extension modules.
Flashing (two times): Failed to apply the settings to the safety extension module.
Flashing (three times): The rotary switch setting was changed during operation.
Flashing (four times): Any of the following errors occurred.
The module was powered ON after the rotary switch setting has been changed in the power OFF state.
The ENTER button is pressed for three seconds or more.
A setting is not applied after changing the position of a module.
Flashing (five times): A power supply error occurred.
Flashing (six times): A self-monitoring error or an internal error occurred.
OFF: No error
I0 LED Green Indicates the input status of I0.
ON: Input ON
Flashing: A process error occurred or synchronous time (1500ms) was exceeded.
Flashing (I0 and I1 flash in phase): A cross-circuit occurred between I0 and I1.
OFF: Input OFF
I1 LED Green Indicates the input status of I1.
ON: Input ON
Flashing: A process error occurred or synchronous time (1500ms) was exceeded.
Flashing (I0 and I1 flash in phase): A cross-circuit occurred between I0 and I1.
OFF: Input OFF
I2 LED Green Indicates the input status of I2.
ON: Input ON
Flashing: A process error occurred or synchronous time (1500ms) was exceeded.
Flashing (I2 and I3 flash in phase): A cross-circuit occurred between I2 and I3.
OFF: Input OFF
I3 LED Green Indicates the input status of I3.
ON: Input ON
Flashing: A process error occurred or synchronous time (1500ms) was exceeded.
Flashing (I2 and I3 flash in phase): A cross-circuit occurred between I2 and I3.
OFF: Input OFF
I4 LED Green Indicates the input status of I4.
ON: Input ON
Flashing: A process error occurred or synchronous time (1500ms) was exceeded.
Flashing (I4 and I5 flash in phase): A cross-circuit occurred between I4 and I5.
OFF: Input OFF
I5 LED Green Indicates the input status of I5.
ON: Input ON
Flashing: A process error occurred or synchronous time (1500ms) was exceeded.
Flashing (I4 and I5 flash in phase): A cross-circuit occurred between I4 and I5.
OFF: Input OFF
I6 LED Green Indicates the input status of I6.
ON: Input ON
Flashing: A process error occurred or synchronous time (1500ms) was exceeded.
Flashing (I6 and I7 flash in phase): A cross-circuit occurred between I6 and I7.
OFF: Input OFF
I7 LED Green Indicates the input status of I7.
ON: Input ON
Flashing: A process error occurred or synchronous time (1500ms) was exceeded.
Flashing (I6 and I7 flash in phase): A cross-circuit occurred between I6 and I7.
OFF: Input OFF
QA LED Green Indicates if the input conditions of INPUT A from input I0 to I3 are satisfied.
ON: Input conditions are satisfied.
OFF: Input OFF
QB LED Green Indicates if the input conditions of INPUT B from input I4 to I7 are satisfied.
ON: Input conditions are satisfied.
OFF: Input OFF