Engineering and remote access
3.6 SITOP UPS Manager
SITOP UPS1600 / UPS1100
Manual, 04.2017, A5E37775406-8-76
123
5. To check whether the application will performed correctly, click the "Start" button.
6. Enter the time in minutes and seconds after which the application should be started.
Note
It is recommended that only applications without user interface
– or those that automatically
exit themselves without any manual intervention
– are started.
Behavior during buffer mode
Make the settings under "Software configuration > Buffer operation" vor.
The following options are available:
● Start application on power failure.
● Start application after power return.
● Show SITOP UPS Manager on power failure.
● Show SITOP UPS Manager after power return.
● Shut down PC on power failure.
If the buffer time (see Section Configuring the SITOP UPS1600 (Page 119)) is set shorter
than this time, the SITOP UPS1600 switches off before the PC has been shut down. The
PC is then no longer protected. In master-slave operation, the time required to run down
the master must be longer than the time required for the slave.