Engineering and remote access
3.8 OPC UA server
SITOP UPS1600 / UPS1100
Manual, 04.2017, A5E37775406-8-76
173
3.8.6.10
Charging
Display name
Data type
Definition
Description
ChargingCurrent
Setpoint
Float AnalogItemType Charge current
ChargeEndVoltage
Setpoint
Float AnalogItemType Battery voltage when charging changes to trickle charging.
Battery is charged 100 %.
3.8.6.11
General
Display name
Data type
Definition
Description
AlarmInvalidSupply
VoltageTimeSetpoint
Float AnalogItemType Alarm filter: an alarm is only sent if it is pending for longer
than the configured time
DeviceOutputEnable
Setpoint
Boolean PropertyType DeviceOutputEnableSetpoint
ResetEnableSetpoint Boolean PropertyType When input voltage returns during buffering, the output is
switched off for a configurable time in order to reset con-
nected devices
ResetTimerSetpoint Byte AnalogItemType
Time for which the output of SITOP UPS1600 is switched off
when connected devices are reset.
ResistorTestInterval
Setpoint
Byte AnalogItemType Battery test interval
3.8.6.12
Hardware
Display name
Data type
Definition
Description
HardwareBattery
ProfileClamp
Enumeration MultiState
DiscreteType
The charge characteristic for batteries on signal terminals is
set. This setting is only applied if hardware settings are
effective.
HardwareBuffer
ThresholdSwitch
Enumeration MultiState
DiscreteType
Trigger voltage for buffering - buffering is activated below
this value
HardwareBuffer
TimeSwitch
Enumeration MultiState
DiscreteType
Desired buffering time before device switches off
HardwareBuffering
EnableClamp
Boolean PropertyType Enable buffering
HardwareEnable
ResetClamp
Boolean PropertyType When input voltage returns during buffering, the output is
switched off for a configurable time in order to reset con-
nected devices
HardwareStartFrom
BatteryClamp
Boolean PropertyType Setting for 'Start from battery' on signal terminal