3.8 OPC UA server
SITOP UPS1600 / UPS1100
Manual, 04.2017, A5E37775406-8-76
165
A subscription can only be made to nodes of NodeClass "Variable" .
3.8.5.2
Changing the value of a node
Write access operations to values are not permitted in order to avoid making undesirable
changes.
Write access is made possible by calling method "InitLock". After 10 seconds, access is
automatically blocked again.
Permitting write access
Note
Write access only for devices with PROFINET interface
Write access via OPC
UA is not supported by devices with USB interface (... - 1AY0).