Engineering and remote access
3.7 Web server
SITOP UPS1600 / UPS1100
Manual, 04.2017, A5E37775406-8-76
137
previously in the state when originally shipped with IP address 0.0.0.0) or using the
already set IP address. Under certain circumstances you must wait approximately 1
minute because a new certificate must be created due to the IP address change.
3. Login with name "admin" and password "admin".
4. Under "HW Configuration -> General -> Web server -> Settings" the web server
must be permanently activated. ("Activate web server on this module").
5. Under "HW Configuration -> General -> Communication interface", IP address,
subnet mask and router address can be set.
6. To transfer changes to the device, the "Download to device" button must be
pressed. Under certain circumstances you must wait approximately 1 minute because
a new certificate must be created due to the IP address change.
7. Now turn the rotary coding switches to the required position.
The device can now be accessed at the previously set IP address or the new IP
address.
Procedure
1. Connect the client (PG, PC) via the PROFINET interface with the CPU.
2. Open the web browser.
In the address dialog box of the web browser, enter the IP address of the
SITOP UPS1600 in the form http://ww.xx.yy.zz (input example: http://192.168.0.14).
The start page of SITOP UPS1600 is opened. You can navigate to further menus from the
start page.